Form No. PDS 569D.72.2
COMMERCIAL AIR-COOLED
CONDENSING UNITS WITH
524A AIR-HANDLING UNITS
FEATURES/BENEFITS
These dependable split systems match Bryant’s indoor-air han-
dlers and direct-expansion coils with outdoor condensing units
for a wide selection of commercial cooling solutions.
CONSTRUCTED FOR LONG LIFE The569D(singlecir-
cuit, scroll compressor), 576C (single circuit semi-hermetic
compressor), 569F/566E (dual circuit, scroll compressor) and
566D (semi-hermetic compressor) models are designed and
built to last. The copper tube-aluminum fin outdoor coil
construction provides years of trouble-free operation. Where
conditions require them, E-coated coils and pre-coated fin coils
are also available. Cabinets are constructed of prepainted
galvanized steel, delivering unparalleled protection from the
environment. Inside and outside surfaces are protected to
ensure long life, good looks, and reliable operation. Safety con-
trols are used for enhanced system protection and reliability.
EFFICIENT OPERATION Building owners will appreciate
the high unit EERs (Energy Efficiency Ratios) offered by these
condensing units. These units provide greater efficiency than
similar units in the marketplace, which translates into year-
round operating savings.
CONTROLS FOR PERFORMANCE DEPENDABILITY — The
condensing units offer the building owner operating controls
and components designed for performance dependability. The
highly efficient hermetic and semi-hermetic compressors are
engineered for long life and durability. The compressors
include overload protection and vibration isolation for enhance-
ment of quiet operation. The high-pressure switch protects the
entire refrigeration system from abnormally high operating
pressures. A low-pressure switch protects the system from
low-pressure conditions, including loss of charge.
The 569F120 and 566E150-240 units feature 2 scroll compres-
sors and 2 refrigerant circuits that provide continuous air
conditioning and design flexibility. These units also include
Cycle-LOC™ anti-short-cycling protection which helps to
protect the units against compressor failure.
All units include a crankcase heater to eliminate liquid slugging
at start-up. Units with semi-hermetic compressors are also
equipped with an oil-level sight glass.
Latest safety standards are assured through UL and UL
Canada approvals.
INNOVATIVE BRYANT PACKAGED AIR HANDLERS ARE
CUSTOM MATCHED TO THE CONDENSING UNITS The
524A Series has excellent fan performance, efficient direct-
expansion (DX) coils, a unique combination of indoor-air qual-
ity features, and easy installation. Its versatility and state-of-
the-art features help to ensure that your split system provides
economical performance now and in the future.
Indoor-Air Quality (IAQ) Features The unique combination
of IAQ features in the 524A Series air handlers help to ensure
that only clean, fresh, conditioned air is delivered to the occu-
pied space.
Direct-expansion (DX) cooling coils prevent the build-up of
humidity in the room, even during part-load conditions. Unit
sizes of 10 tons and above feature dual-circuit coils for
improved temperature control.
Standard 2-in. disposable filters remove dust and airborne par-
ticles from the occupied space for cleaner air.
Models 566D, 566E, 569D,
569F, 576C
with 524A
6to20Tons
569D072-120
576C120
569F120
566D150-240
566E150-240
524A072-300
Seitenansicht 0
1 2 3 4 5 6 ... 83 84

Inhaltsverzeichnis

Seite 1 - 6to20Tons

Form No. PDS 569D.72.2COMMERCIAL AIR-COOLEDCONDENSING UNITS WITH524A AIR-HANDLING UNITSFEATURES/BENEFITSThese dependable split systems match Bryant’s

Seite 2 - TABLE OF CONTENTS

10TYPICAL WIRING SCHEMATICS (cont)LEGENDAHA — Adjustable HeatAnticipatorC—Contactor,CompressorCAP — CapacitorCB — Circuit BreakerCC — Cooling Compensa

Seite 3 - ARI* CAPACITY RATINGS

11MODEL NUMBER NOMENCLATURE569D P X 072 000 ––Voltage DesignationE — 460-3-60P — 208/230-3-60T— 575-3-60HeatingX—NoneNominal Tons Cooling072 — 6 (569D

Seite 4 - OPTIONS AND ACCESSORIES

12PHYSICAL DATA569D072-120, 576C120, 569F120 UNITS*Unit is factory-supplied with holding charge only.†Typical operating charge with 25 ft of interconn

Seite 5

13DIMENSIONS569D072-120, 576C120UNITALUMINUM COILStandard Unit Weight Corner W Corner X Corner Y Corner Z Center of Gravitylb kglbkglbkglbkglbkg X mm

Seite 6 - 524A with Condensate Trap

14DIMENSIONS (cont)CONVENIENCEOUTLET LOCATIONELECTRICAL DISCONNECTLOCATIONCONTROL BOXACCESS PANELCORNER “D”CORNER “A”CORNER “B”CORNER “C”OUTDOOR COILO

Seite 7 - SELECTION PROCEDURE

15PERFORMANCE DATACONDENSING UNIT RATINGSLEGEND569D072SST (F)Air Temperature Entering Condenser (F)80 85 95 100 105 11525TC 53.6 52.3 49.4 48.0 46.5 4

Seite 8 - CONTROLS

16PERFORMANCE DATA (cont)COMBINATION RATINGS*UNIT 569D072LEGEND*Combinations on this page are ENERGY STAR® compliant.569D072/524A-C072 WITH HIGH-CAPAC

Seite 9 - TYPICAL WIRING SCHEMATICS

17PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D072 (cont)LEGEND*This combination is ENERGY STA R ® compliant.569D072/524A-C090 WITH HIGH-

Seite 10

18PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D090LEGEND*This combination is ENERGY STA R ® compliant.569D090/524A-C072 WITH HIGH-CAPACIT

Seite 11 - Quality Assurance

19PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D090 (cont)LEGEND*This combination is ENERGY STA R ® compliant.569D090/524A-C090 WITH HIGH-

Seite 12 - 50TFQ004-012

2Thermal insulation contains an EPA-registered immobilizedanti-microbial agent to inhibit the growth of bacteria and fungi.The pitched, non-corroding

Seite 13 - DIMENSIONS

20PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D120LEGEND569D120/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 14 - DIMENSIONS (cont)

21PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D120 (cont)LEGEND569D120/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 15 - PERFORMANCE DATA

22PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 576C120LEGEND576C120/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 16 - PERFORMANCE DATA (cont)

23PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 576C120 (cont)LEGEND576C120/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 17

24PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569F120LEGEND569F120/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 18

25PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569F120 (cont)LEGEND569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 19

26ELECTRICAL DATA569D072-120, 576C120, 569F120 UNITSLEGEND *Units are suitable for use on electrical systems where voltage suppliedto the unit termina

Seite 20

27APPLICATION DATA — 569D072-120, 576C090-120, 569F120OPERATING LIMITSNOTES:1. Select air handler at no less than 300 cfm/ton (nominal condens-ing uni

Seite 21

28TYPICAL PIPING AND WIRINGCONDENSINGUNITFIELDSUPPLIEDPOWERINSULATEDVAPORLINEPITCHWEATHERPROOFFUSED DISCONNECT*PER NECPOWER WIRESMOISTUREINDICATORSIGH

Seite 22

29GUIDE SPECIFICATIONS — 569D072-120, 576C120COMMERCIAL AIR-COOLED CONDENSING UNITSHVAC GUIDE SPECIFICATIONSSIZE RANGE: 6 TO 10 TONS, NOMINALBRYANT MO

Seite 23

3ARI* CAPACITY RATINGSLEGEND*Air Conditioning and Refrigeration Institute.†Ratings in accordance with latest ARI Standard revisions.**Condensing unit

Seite 24

30GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont)J. Special Features:1. Low-Ambient Temperature Control Accessory:Low-ambient control shall be avai

Seite 25

31GUIDE SPECIFICATIONS — 569F120COMMERCIAL AIR-COOLED CONDENSING UNITSHVAC GUIDE SPECIFICATIONSSIZE RANGE: 10 TONS, NOMINALBRYANT MODEL NUMBER: 569F,

Seite 26 - ELECTRICAL DATA

32GUIDE SPECIFICATIONS — 569F120 (cont)3. Optional Condenser Coil Materials:a. Pre-Coated Aluminum-Fin Coils:Shall have a durable epoxy-phenolic coati

Seite 27

33MODEL NUMBER NOMENCLATURE566D E X 150 000––Nominal Tons Cooling150 — 12-1/2180 — 15240 — 20Heating Capacity000 — No HeatFactory-Installed Options*He

Seite 28 - TYPICAL PIPING AND WIRING

34PHYSICAL DATA566D150-240 UNITS*Unit is factory-supplied with holding charge only.†Typical operating charge with 25 ft of interconnecting piping. Ope

Seite 29

35PHYSICAL DATA (cont)566E150-240 UNITS*Unit is factory-supplied with holding charge only.†Typical operating charge with 25 ft of interconnecting pipi

Seite 30

36DIMENSIONS566D150-240NOTES:1. Service clearances are as follows:Side (compressor) — 31/2ftSide (opposite compressor) — 3 ftEnds—2ftTop—5ft2. See pag

Seite 31

37DIMENSIONS (cont)NOTES:1. Service clearances are as follows:Side (compressor) — 31/2ft (1067 mm)Side (opposite compressor) — 3 ft (914 mm)Ends — 2 f

Seite 32

38DIMENSIONS (cont)566D150-240, 566E150-240566D150-240UNIT566DALUMINUM COILStandardWeight(lb)Operational Weight Points (lb)ABCD E F150 779 70 177 68 1

Seite 33

39PERFORMANCE DATACONDENSING UNIT RATINGSLEGEND566D150SST (F)Air Temperature Entering Condenser (F)80 85 95 100 105 11525TC 101.0 97.6 90.0 86.0 82.2

Seite 34 - 566D/E150-240

4OPTIONS AND ACCESSORIES566D, 566E, 569D, 569F, 576C FACTORY-INSTALLEDOPTIONSDura-ShieldCondenser Coils offer several options to matchcoil protection

Seite 35 - PHYSICAL DATA (cont)

40PERFORMANCE DATA (cont)COMBINATION RATINGSUNIT 566D150LEGEND566D150/524A-C150 WITH HIGH CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)Evapora

Seite 36

41PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D150 (cont)LEGEND566D150/524A-C180 WITH HIGH CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 37

42PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D180LEGEND566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 38

43PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D180 (cont)LEGEND566D180/524A-C240 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 39

44PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D240LEGEND566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 40

45PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E150LEGEND566E150/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 41

46PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E150 (cont)LEGEND566E150/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 42

47PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E150 (cont)LEGEND566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 43

48PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E180LEGEND566E180/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 44

49PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E180 (cont)LEGEND566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 45

5OPTIONS AND ACCESSORIES (cont)524A-B, C FACTORY-INSTALLED OPTIONSAlternate Fan Motors and Drives are available to provide thewidest possible range of

Seite 46

50PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E180 (cont)LEGEND566E180/524A-C240 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 47

51PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E240LEGEND566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)

Seite 48

52PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E240 (cont)LEGEND566E240/524A-C300 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens

Seite 49

53ELECTRICAL DATA566D150-240LEGEND *Units are suitable for use on electrical systems where voltage supplied to theunit terminals is not below or above

Seite 50

54APPLICATION DATA — 566D150-240, 566E150-2401. INSTALLATION — Select equipment to match or to beslightly less than peak load. This provides better hu

Seite 51

55APPLICATION DATA — 566D150-240, 566E150-240 (cont)REFRIGERANT PIPING SIZESLEGENDClose-coupled.*Requires a double suction riser if 2 unloaders are us

Seite 52

56APPLICATION DATA — 566D150-240, 566E150-240 (cont)MULTIPLE CONDENSING UNIT ARRANGEMENTS*Space for Service and Airflow*For clearances between control

Seite 53

57TYPICAL PIPING AND WIRINGLEGEND*Field supplied.NEC — National Electrical CodeTXV—Thermostatic Expansion ValvePipingNOTES:1. All piping must follow s

Seite 54

58TYPICAL PIPING AND WIRING (cont)LEGEND*Field supplied.NEC — National Electrical CodeTXV—Thermostatic Expansion ValvePipingNOTES:1. All piping must f

Seite 55

59GUIDE SPECIFICATIONS — 566D150-240, 566E150-240COMMERCIAL AIR-COOLED CONDENSING UNITSHVAC GUIDE SPECIFICATIONSSIZE RANGE: 121/2TO 20 TONS, NOMINALBR

Seite 56

6OPTIONS AND ACCESSORIES (cont)DISCHARGEPLENUMRETURN-AIRGRILLESUBBASEFANCOILUNITECONOMIZERFAN COIL UNITFAN COILUNITHOT WATER ORSTEAM COIL524A with Eco

Seite 57

60GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 (cont)Manual reset at the unitElectrical overload protection through the use of def-inite-purpose co

Seite 58

61MODEL NUMBER NOMENCLATURE524A P B 120 000 GC524A — Fan CoilVoltageE — 460-3-60†J — 208/230-1-60 (Sizes 072, 090 Only)P — 208/230-3-60T — 575-3-60Coi

Seite 59

62PHYSICAL DATA524A-B,C UNITSLEGEND*Refer to Alternate Fan Motor Data table, page 80, for alternate motor data.†Units are shipped without refrigerant

Seite 60

63DIMENSIONS524A-B,C072-120UNITUNIT WEIGHT(lb)524A-B072 381524A-B090 385524A-B120 405524A-C072 399524A-C090 404524A-C120 425LEGENDNOTES:1. Dimensions

Seite 61

64DIMENSIONS (cont)524A-B,C150-240.UNIT524AUNITWEIGHT(lb)B150 670B180 685B240 690C150 695C180 713C240 730LEGENDNOTES:1. Dimensions in [ ] are in milli

Seite 62 - 524A072-300

65DIMENSIONS (cont)524A-B,C300CONTROL BOXCONTROL BOXALTERNATEACCESSFOR FILTERSRETURN AIROPENINGALTERNATEACCESS FORMOTOR/BELTUNIT524AUNITWEIGHT(lb)B300

Seite 63

66PERFORMANCE DATA524A-B FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP See Legend and Notes on page 67.UNIT524A-BAIRFLOW(Cfm)EXTERNAL STATIC PRESSURE (in.

Seite 64

67PERFORMANCE DATA (cont)524A-B FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESPLEGENDBoldindicates field-supplied drive is required.Plain type indicates sta

Seite 65

68PERFORMANCE DATA (cont)FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL —0.0-1.2 in. wg ESPSee Legend and Notes on page 69.UNIT524A-C(High-Capa

Seite 66

69PERFORMANCE DATA (cont)FAN PERFORMANCE DATA — 524A-CWITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESPLEGENDBoldindicates field-supplied drive is required

Seite 67

7SELECTION PROCEDURETo determine combination ratings for 569D/F, 576C and 566D/Eunits matched with 524A Series air handlers, follow these steps:I DETE

Seite 68

70PERFORMANCE DATA (cont)FACTORY-SUPPLIED FILTER PRESSURE DROP ACCESSORY PLENUM AIR THROW DATAThrow distances shown are for 75 fpm terminal velocity.

Seite 69

71PERFORMANCE DATA (cont)HYDRONIC HEATING CAPACITIESLEGEND*Based on 5 psig steam, 60 F entering-air temperature. All steam coilsare non-freeze type.†B

Seite 70

72ELECTRICAL DATA524A-B,C STANDARD MOTORSSee Legend and Notes on page 73.UNIT524A-B524A-CV*-PH-HzVOLTAGELIMITSFAN MOTOR POWER SUPPLYHp (kW) FLAMinimum

Seite 71

73ELECTRICAL DATA (cont)524A-B,C ALTERNATE MOTORSLEGEND*Motors are designed for satisfactory operation within 10% of nominalvoltages shown. Voltages s

Seite 72

74ELECTRICAL DATA (cont)ELECTRIC HEATER DATASee Legend and Notes on page 75.HEATER PART NO. UNIT V-PH-HzFAN M OTORELECTRIC HEATER(S)MCA* MOCP*NominalC

Seite 73 - ELECTRICAL DATA (cont)

75ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)LEGEND*Values shown are for single-point connection of electric heat acces-sory and air handler.†Si

Seite 74

76ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)See Legend and Notes on page 77.HEATER PART NO. UNIT V-PH-HzFAN MOTORELECTRIC HEATER(S)MCA* MOCP*No

Seite 75

77ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)LEGEND*Values shown are for single-point connection of electric heat acces-sory and air handler.NOT

Seite 76

78ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)LEGEND*Values shown are for single-point connection of electric heat acces-sory and air handler.NOT

Seite 77

79APPLICATION DATA — 524A1. OPERATING LIMITSMaximum fan speed — 524A-B,C072-240 . . . . . . . .1200 rpmMaximum fan speed — 524A-B,C300 . . . 1100 rpm

Seite 78

8CONTROLSOPERATING SEQUENCES569D072-120, 576C120 — At start-up, the thermostat calls forcooling. With all safety devices satisfied, the compressorcont

Seite 79 - APPLICATION DATA — 524A

80APPLICATION DATA — 524A (cont)FAN MOTOR DATA (cont)ALTERNATE MOTORLEGENDNEMA — National Electrical Manufacturers AssociationSTANDARD DRIVE DATA*Four

Seite 80

81APPLICATION DATA — 524A (cont)MEDIUM-STATIC DRIVE DATA*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley settin

Seite 81

82GUIDE SPECIFICATIONS — 524ACOMMERCIAL PACKAGED AIR-HANDLING UNITHVAC GUIDE SPECIFICATIONSSIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO25 TON

Seite 82 - GUIDE SPECIFICATIONS — 524A

83GUIDE SPECIFICATIONS — 524A (cont)5. Electric Heaters:Heaters for nominal 240, 480, or 575-volt, 3-phase,60 Hz power supply shall be factory-supplie

Seite 83

Copyright 2004 Bryant Heating & Cooling Systems Printed in U.S.A. 7/04 Catalog No. 5256-904SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT MUS

Seite 84

9TYPICAL WIRING SCHEMATICS569D090, 208/230-3-360 and 460-3-60 UnitsNOTES:1. If any of the original wire furnished must bereplaced, it must be replaced