Form No. PDS 569D.72.2COMMERCIAL AIR-COOLEDCONDENSING UNITS WITH524A AIR-HANDLING UNITSFEATURES/BENEFITSThese dependable split systems match Bryant’s
10TYPICAL WIRING SCHEMATICS (cont)LEGENDAHA — Adjustable HeatAnticipatorC—Contactor,CompressorCAP — CapacitorCB — Circuit BreakerCC — Cooling Compensa
11MODEL NUMBER NOMENCLATURE569D P X 072 000 ––Voltage DesignationE — 460-3-60P — 208/230-3-60T— 575-3-60HeatingX—NoneNominal Tons Cooling072 — 6 (569D
12PHYSICAL DATA569D072-120, 576C120, 569F120 UNITS*Unit is factory-supplied with holding charge only.†Typical operating charge with 25 ft of interconn
13DIMENSIONS569D072-120, 576C120UNITALUMINUM COILStandard Unit Weight Corner W Corner X Corner Y Corner Z Center of Gravitylb kglbkglbkglbkglbkg X mm
14DIMENSIONS (cont)CONVENIENCEOUTLET LOCATIONELECTRICAL DISCONNECTLOCATIONCONTROL BOXACCESS PANELCORNER “D”CORNER “A”CORNER “B”CORNER “C”OUTDOOR COILO
15PERFORMANCE DATACONDENSING UNIT RATINGSLEGEND569D072SST (F)Air Temperature Entering Condenser (F)80 85 95 100 105 11525TC 53.6 52.3 49.4 48.0 46.5 4
16PERFORMANCE DATA (cont)COMBINATION RATINGS*UNIT 569D072LEGEND*Combinations on this page are ENERGY STAR® compliant.569D072/524A-C072 WITH HIGH-CAPAC
17PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D072 (cont)LEGEND*This combination is ENERGY STA R ® compliant.569D072/524A-C090 WITH HIGH-
18PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D090LEGEND*This combination is ENERGY STA R ® compliant.569D090/524A-C072 WITH HIGH-CAPACIT
19PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D090 (cont)LEGEND*This combination is ENERGY STA R ® compliant.569D090/524A-C090 WITH HIGH-
2Thermal insulation contains an EPA-registered immobilizedanti-microbial agent to inhibit the growth of bacteria and fungi.The pitched, non-corroding
20PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D120LEGEND569D120/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
21PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569D120 (cont)LEGEND569D120/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
22PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 576C120LEGEND576C120/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
23PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 576C120 (cont)LEGEND576C120/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
24PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569F120LEGEND569F120/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
25PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 569F120 (cont)LEGEND569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
26ELECTRICAL DATA569D072-120, 576C120, 569F120 UNITSLEGEND *Units are suitable for use on electrical systems where voltage suppliedto the unit termina
27APPLICATION DATA — 569D072-120, 576C090-120, 569F120OPERATING LIMITSNOTES:1. Select air handler at no less than 300 cfm/ton (nominal condens-ing uni
28TYPICAL PIPING AND WIRINGCONDENSINGUNITFIELDSUPPLIEDPOWERINSULATEDVAPORLINEPITCHWEATHERPROOFFUSED DISCONNECT*PER NECPOWER WIRESMOISTUREINDICATORSIGH
29GUIDE SPECIFICATIONS — 569D072-120, 576C120COMMERCIAL AIR-COOLED CONDENSING UNITSHVAC GUIDE SPECIFICATIONSSIZE RANGE: 6 TO 10 TONS, NOMINALBRYANT MO
3ARI* CAPACITY RATINGSLEGEND*Air Conditioning and Refrigeration Institute.†Ratings in accordance with latest ARI Standard revisions.**Condensing unit
30GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont)J. Special Features:1. Low-Ambient Temperature Control Accessory:Low-ambient control shall be avai
31GUIDE SPECIFICATIONS — 569F120COMMERCIAL AIR-COOLED CONDENSING UNITSHVAC GUIDE SPECIFICATIONSSIZE RANGE: 10 TONS, NOMINALBRYANT MODEL NUMBER: 569F,
32GUIDE SPECIFICATIONS — 569F120 (cont)3. Optional Condenser Coil Materials:a. Pre-Coated Aluminum-Fin Coils:Shall have a durable epoxy-phenolic coati
33MODEL NUMBER NOMENCLATURE566D E X 150 000––Nominal Tons Cooling150 — 12-1/2180 — 15240 — 20Heating Capacity000 — No HeatFactory-Installed Options*He
34PHYSICAL DATA566D150-240 UNITS*Unit is factory-supplied with holding charge only.†Typical operating charge with 25 ft of interconnecting piping. Ope
35PHYSICAL DATA (cont)566E150-240 UNITS*Unit is factory-supplied with holding charge only.†Typical operating charge with 25 ft of interconnecting pipi
36DIMENSIONS566D150-240NOTES:1. Service clearances are as follows:Side (compressor) — 31/2ftSide (opposite compressor) — 3 ftEnds—2ftTop—5ft2. See pag
37DIMENSIONS (cont)NOTES:1. Service clearances are as follows:Side (compressor) — 31/2ft (1067 mm)Side (opposite compressor) — 3 ft (914 mm)Ends — 2 f
38DIMENSIONS (cont)566D150-240, 566E150-240566D150-240UNIT566DALUMINUM COILStandardWeight(lb)Operational Weight Points (lb)ABCD E F150 779 70 177 68 1
39PERFORMANCE DATACONDENSING UNIT RATINGSLEGEND566D150SST (F)Air Temperature Entering Condenser (F)80 85 95 100 105 11525TC 101.0 97.6 90.0 86.0 82.2
4OPTIONS AND ACCESSORIES566D, 566E, 569D, 569F, 576C FACTORY-INSTALLEDOPTIONSDura-ShieldCondenser Coils offer several options to matchcoil protection
40PERFORMANCE DATA (cont)COMBINATION RATINGSUNIT 566D150LEGEND566D150/524A-C150 WITH HIGH CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)Evapora
41PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D150 (cont)LEGEND566D150/524A-C180 WITH HIGH CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
42PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D180LEGEND566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
43PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D180 (cont)LEGEND566D180/524A-C240 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
44PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566D240LEGEND566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
45PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E150LEGEND566E150/524A-C120 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
46PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E150 (cont)LEGEND566E150/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
47PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E150 (cont)LEGEND566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
48PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E180LEGEND566E180/524A-C150 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
49PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E180 (cont)LEGEND566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
5OPTIONS AND ACCESSORIES (cont)524A-B, C FACTORY-INSTALLED OPTIONSAlternate Fan Motors and Drives are available to provide thewidest possible range of
50PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E180 (cont)LEGEND566E180/524A-C240 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
51PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E240LEGEND566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondenser(Edb)
52PERFORMANCE DATA (cont)COMBINATION RATINGS (cont)UNIT 566E240 (cont)LEGEND566E240/524A-C300 WITH HIGH-CAPACITY 4-ROW COILTemp (F)Air EnteringCondens
53ELECTRICAL DATA566D150-240LEGEND *Units are suitable for use on electrical systems where voltage supplied to theunit terminals is not below or above
54APPLICATION DATA — 566D150-240, 566E150-2401. INSTALLATION — Select equipment to match or to beslightly less than peak load. This provides better hu
55APPLICATION DATA — 566D150-240, 566E150-240 (cont)REFRIGERANT PIPING SIZESLEGENDClose-coupled.*Requires a double suction riser if 2 unloaders are us
56APPLICATION DATA — 566D150-240, 566E150-240 (cont)MULTIPLE CONDENSING UNIT ARRANGEMENTS*Space for Service and Airflow*For clearances between control
57TYPICAL PIPING AND WIRINGLEGEND*Field supplied.NEC — National Electrical CodeTXV—Thermostatic Expansion ValvePipingNOTES:1. All piping must follow s
58TYPICAL PIPING AND WIRING (cont)LEGEND*Field supplied.NEC — National Electrical CodeTXV—Thermostatic Expansion ValvePipingNOTES:1. All piping must f
59GUIDE SPECIFICATIONS — 566D150-240, 566E150-240COMMERCIAL AIR-COOLED CONDENSING UNITSHVAC GUIDE SPECIFICATIONSSIZE RANGE: 121/2TO 20 TONS, NOMINALBR
6OPTIONS AND ACCESSORIES (cont)DISCHARGEPLENUMRETURN-AIRGRILLESUBBASEFANCOILUNITECONOMIZERFAN COIL UNITFAN COILUNITHOT WATER ORSTEAM COIL524A with Eco
60GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 (cont)Manual reset at the unitElectrical overload protection through the use of def-inite-purpose co
61MODEL NUMBER NOMENCLATURE524A P B 120 000 GC524A — Fan CoilVoltageE — 460-3-60†J — 208/230-1-60 (Sizes 072, 090 Only)P — 208/230-3-60T — 575-3-60Coi
62PHYSICAL DATA524A-B,C UNITSLEGEND*Refer to Alternate Fan Motor Data table, page 80, for alternate motor data.†Units are shipped without refrigerant
63DIMENSIONS524A-B,C072-120UNITUNIT WEIGHT(lb)524A-B072 381524A-B090 385524A-B120 405524A-C072 399524A-C090 404524A-C120 425LEGENDNOTES:1. Dimensions
64DIMENSIONS (cont)524A-B,C150-240.UNIT524AUNITWEIGHT(lb)B150 670B180 685B240 690C150 695C180 713C240 730LEGENDNOTES:1. Dimensions in [ ] are in milli
65DIMENSIONS (cont)524A-B,C300CONTROL BOXCONTROL BOXALTERNATEACCESSFOR FILTERSRETURN AIROPENINGALTERNATEACCESS FORMOTOR/BELTUNIT524AUNITWEIGHT(lb)B300
66PERFORMANCE DATA524A-B FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP See Legend and Notes on page 67.UNIT524A-BAIRFLOW(Cfm)EXTERNAL STATIC PRESSURE (in.
67PERFORMANCE DATA (cont)524A-B FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESPLEGENDBoldindicates field-supplied drive is required.Plain type indicates sta
68PERFORMANCE DATA (cont)FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL —0.0-1.2 in. wg ESPSee Legend and Notes on page 69.UNIT524A-C(High-Capa
69PERFORMANCE DATA (cont)FAN PERFORMANCE DATA — 524A-CWITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESPLEGENDBoldindicates field-supplied drive is required
7SELECTION PROCEDURETo determine combination ratings for 569D/F, 576C and 566D/Eunits matched with 524A Series air handlers, follow these steps:I DETE
70PERFORMANCE DATA (cont)FACTORY-SUPPLIED FILTER PRESSURE DROP ACCESSORY PLENUM AIR THROW DATAThrow distances shown are for 75 fpm terminal velocity.
71PERFORMANCE DATA (cont)HYDRONIC HEATING CAPACITIESLEGEND*Based on 5 psig steam, 60 F entering-air temperature. All steam coilsare non-freeze type.†B
72ELECTRICAL DATA524A-B,C STANDARD MOTORSSee Legend and Notes on page 73.UNIT524A-B524A-CV*-PH-HzVOLTAGELIMITSFAN MOTOR POWER SUPPLYHp (kW) FLAMinimum
73ELECTRICAL DATA (cont)524A-B,C ALTERNATE MOTORSLEGEND*Motors are designed for satisfactory operation within 10% of nominalvoltages shown. Voltages s
74ELECTRICAL DATA (cont)ELECTRIC HEATER DATASee Legend and Notes on page 75.HEATER PART NO. UNIT V-PH-HzFAN M OTORELECTRIC HEATER(S)MCA* MOCP*NominalC
75ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)LEGEND*Values shown are for single-point connection of electric heat acces-sory and air handler.†Si
76ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)See Legend and Notes on page 77.HEATER PART NO. UNIT V-PH-HzFAN MOTORELECTRIC HEATER(S)MCA* MOCP*No
77ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)LEGEND*Values shown are for single-point connection of electric heat acces-sory and air handler.NOT
78ELECTRICAL DATA (cont)ELECTRIC HEATER DATA (cont)LEGEND*Values shown are for single-point connection of electric heat acces-sory and air handler.NOT
79APPLICATION DATA — 524A1. OPERATING LIMITSMaximum fan speed — 524A-B,C072-240 . . . . . . . .1200 rpmMaximum fan speed — 524A-B,C300 . . . 1100 rpm
8CONTROLSOPERATING SEQUENCES569D072-120, 576C120 — At start-up, the thermostat calls forcooling. With all safety devices satisfied, the compressorcont
80APPLICATION DATA — 524A (cont)FAN MOTOR DATA (cont)ALTERNATE MOTORLEGENDNEMA — National Electrical Manufacturers AssociationSTANDARD DRIVE DATA*Four
81APPLICATION DATA — 524A (cont)MEDIUM-STATIC DRIVE DATA*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley settin
82GUIDE SPECIFICATIONS — 524ACOMMERCIAL PACKAGED AIR-HANDLING UNITHVAC GUIDE SPECIFICATIONSSIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO25 TON
83GUIDE SPECIFICATIONS — 524A (cont)5. Electric Heaters:Heaters for nominal 240, 480, or 575-volt, 3-phase,60 Hz power supply shall be factory-supplie
Copyright 2004 Bryant Heating & Cooling Systems Printed in U.S.A. 7/04 Catalog No. 5256-904SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT MUS
9TYPICAL WIRING SCHEMATICS569D090, 208/230-3-360 and 460-3-60 UnitsNOTES:1. If any of the original wire furnished must bereplaced, it must be replaced