NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
Index Page
SAFETY CONSIDERATIONS.....................................................2
DIMENSIONAL DRAWING........................................................3
Clearances to Combustibles......................................................4
CODES AND STANDARDS........................................................5
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........5
INTRODUCTION..........................................................................6
APPLICATIONS............................................................................6
General ......................................................................................6
Upflow Applications.................................................................6
Downflow Applications............................................................8
Horizontal Left (Supply-Air Discharge) Applications ..........10
Horizontal Right (Supply-Air Discharge) Applications ........12
LOCATION..................................................................................13
General ....................................................................................13
Low-Heat Only Installation....................................................14
Furnace Location Relative to Cooling Equipment ................15
Hazardous Locations...............................................................15
INSTALLATION.........................................................................15
Leveling Legs (If Desired).....................................................15
Installation In Upflow or Downflow Applications................15
Installation In Horizontal Applications..................................17
Air Ducts.................................................................................18
General Requirements .......................................................18
Ductwork Acoustical Treatment .......................................18
Supply Air Connections ....................................................18
Return Air Connections.....................................................18
Filter Arrangement..................................................................18
Bottom Closure Panel.............................................................19
Gas Piping...............................................................................19
Electrical Connections ............................................................20
115-v Wiring......................................................................20
24-v Wiring........................................................................22
Accessories ........................................................................22
Direct Venting.........................................................................22
Removal of Existing Furnaces from
Common Vent Systems................................................22
Combustion-Air and Vent Piping .....................................25
Concentric Vent and Combustion-Air Termination
Kit Installation..............................................................31
Multiventing and Vent Terminations................................34
Condensate Drain....................................................................34
General...............................................................................34
Application.........................................................................34
Condensate Drain Protection.............................................35
START-UP, ADJUSTMENTS AND SAFETY CHECK......35
General...............................................................................35
Select Setup Switch Positions...........................................36
Prime Condensate Trap With Water.................................37
Purge Gas Lines ................................................................37
Sequence of Operation ......................................................37
Single-Stage Thermostat and Two-Stage Heating
(Adaptive Mode) ..........................................................37
Two-Stage Thermostat and Two-Stage Heating.........39
Cooling Mode ...............................................................39
Thermidistat Mode.......................................................40
Super-Dehumidify Mode..............................................40
Continuous Blower Mode............................................40
Heat Pump....................................................................41
Component Test ...........................................................41
Adjustments .......................................................................41
Set Gas Input Rate.......................................................41
Set Temperature Rise...................................................48
Set Thermostat Heat Anticipator.................................49
A93040
ama
CERTIFIED
®
REGISTERED
ISO 9001:2000
As an ENERGY STAR®
Partner, Bryant Heating &
Cooling Systems has de-
termined that this product
meets the ENERGY
STAR® guidelines for en-
ergy efficiency.
Fig. 1—Multipoise Orientations
A93041
UPFLOW
DOWNFLOW
HORIZONTAL
LEFT
AIRFLOW
AIRFLOW
AIRFLOW
AIRFLOW
HORIZONTAL
RIGHT
installation, start-up,
and operating instructions
DELUXE 4-WAY MULTIPOISE
VARIABLE-CAPACITY DIRECT-VENT
CONDENSING GAS FURNACE
Cancels: II 355M-40-13 II 355M-40-14
3-05
355MAV
Series I
—1—
Seitenansicht 0
1 2 3 4 5 6 ... 51 52

Inhaltsverzeichnis

Seite 1 - Series I

NOTE: Read the entire instruction manual before starting theinstallation.This symbol → indicates a change since the last issue.Index PageSAFETY CONSID

Seite 2

2. Extend collector box pressure tube (green label) which waspreviously connected to condensate trap relief port connec-tion by splicing to small diam

Seite 3 - DIMENSIONS (IN.)

WARNING: CARBON MONOXIDE POISONINGHAZARDFailure to follow this warning could result in personalinjury or death.Casing hole filler cap must be installe

Seite 4 - INSTALLATION

3. Route extended tube:a. Behind inducer housing.b. Between blower shelf and inducer housing.4. Determine appropriate length, cut, and reconnect tube

Seite 5

WARNING: CARBON MONOXIDE POISONINGHAZARDFailure to follow this warning could result in personalinjury or death.Casing hole filler cap must be installe

Seite 6

NOTE: For upflow/downflow applications install furnace so thatit is level or pitched forward within 1/2-in. for proper furnaceoperation. For horizonta

Seite 7 - 2 -IN. CPVC STREET

III. FURNACE LOCATION RELATIVE TO COOLINGEQUIPMENTThe cooling coil must be installed parallel with or on downstreamside of furnace to avoid condensati

Seite 8

TABLE 1—OPENING DIMENSIONS (IN.)FURNACECASINGWIDTHAPPLICATIONPLENUM OPENING FLOOR OPENINGABCD17-1/2Upflow Applications 16 24-1/8 16-5/8 24-3/4Downflow

Seite 9

CAUTION: UNIT MAY NOT OPERATEFailure to follow this caution may result in intermittentunit operation or performance satisfaction.Do not bend duct flan

Seite 10

CAUTION: UNIT MAY NOT OPERATEFailure to follow this caution may result in intermittentunit operation or performance satisfaction.The entire length of

Seite 11

CAUTION: CUT HAZARDFailure to follow this caution may result in minorpersonal injury.Use care when cutting support rods in filters to protectagainst f

Seite 12 - pipe section is recommended

Check Safety Controls...49Check Primary Limit Control...49Check

Seite 13

straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Jointcompound (pipe dope) should be applied sparingly and only tomale threads of joints. P

Seite 14

WARNING: FIRE HAZARDFailure to follow this warning could result in intermittentoperation or performance satisfaction.Do not connect aluminum wire betw

Seite 15 - TO BURNERS

WARNING: FIRE OR ELECTRICAL SHOCKHAZARDFailure to follow this warning could result in intermittentunit operation or performance satisfaction.If manual

Seite 16

Fig. 31—Unit Wiring DiagramA02291LEGENDJUNCTIONTERMINALCONTROL TERMINALFACTORY POWER WIRING (115VAC)FACTORY CONTROL WIRING (24VAC)FIELD CONTROL WIRING

Seite 17

WARNING: CARBON MONOXIDE POISONING HAZARDFailure to follow the steps outlined below for each appliance connected to the venting system being placed in

Seite 18

Vent system or vent connectors may need to be resized. For anyother appliances when resizing vent systems or vent connectors,system or connector must

Seite 19 - 2-IN. WIDE

Table 6—Direct Vent Termnination ClearanceA05009AXBVVVVXXAIR SUPPLY INLETVVENT TERMINALAREA WHERE TERMINAL IS NOT PERMITEDABBBBCDEFJILHKG25--24--65--2

Seite 20 - 9-2 NFPA 54-2002

WARNING: FIRE AND EXPLOSION HAZARDFailure to follow this warning could result in fire,property damage, personal injury, or death.Solvent cements are c

Seite 21

NOTE: Moisture in combustion-air intake may be result ofimproper termination. Ensure combustion-air intake pipe termina-tion is similar to that shown

Seite 22

TABLE 7—MAXIMUM ALLOWABLE PIPE LENGTH (FT)ALTITUDEUNITSIZETERMINATIONTYPEPIPE DIAMETER(IN.)*NUMBER OF 90° ELBOWS1234560 to 20000420402 Pipe or 2-In.Co

Seite 23 - Fig. 31—Unit Wiring Diagram

Fig. 2—Dimensional DrawingDIMENSIONS (IN.)UNIT SIZE A D E042040* 24-1/2* 22-7/8* 23*042060 17-1/2 15-7/8 16042080 21 19-3/8 19-1/2060080 21 19-3/8 19-

Seite 24

TABLE 7—MAXIMUM ALLOWABLE PIPE LENGTH (FT) ContinuedALTITUDEUNITSIZETERMINATIONTYPEPIPE DIAMETER(IN.)*NUMBER OF 90° ELBOWS1234566001 to 7000‡0420402 P

Seite 25

6. Clean and dry all surfaces to be joined.7. Check dry fit of pipe and mark insertion depth on pipe.NOTE: It is recommended that all pipes be cut, pr

Seite 26

Fig. 40—Sidewall Termination of 12 in. or MoreA87225MAINTAIN 12 IN.CLEARANCEABOVE HIGHESTANTICIPATED SNOWLEVEL OR GRADE,WHICHEVER ISGREATER.90°V

Seite 27

Fig. 45—Sidewall Termination of 12 in. or Less(Dimension "A" is Touching or 2-In.Maximum Separation)A96129ACOMBUSTION AIRCOMBUSTION AIRVEN

Seite 28

a. Comply with all clearance requirements as stated inTable 6.b. Termination kit should be positioned where vent vaporswill not damage plants/shrubs o

Seite 29 - See notes on next page

WARNING: PERSONAL INJURY ANDPROPERTY DAMAGE HAZARDFailure to follow this warning could result in propertydamage and personal injury or death.Caution s

Seite 30

CAUTION: UNIT MAY NOT OPERATEFailure to follow this caution may result in intermittentunit operation or performance satisfaction.These furnaces are eq

Seite 31

4. Replace main furnace door and blower access panel.NOTE: If a bypass humidifier is used, setup switch SW1-3 (LowHEAT Rise Adjust) should be in ON po

Seite 32

NOTE: Low-heat-only switch, SW1-2, selects either the low-heat-only operation mode when ON, (see item 2. below) oradaptive heating mode when OFF, in r

Seite 33 - OMBUSTION AIR

115 vac power to the furnace, or by interrupting 24 vacpower at SEC1 or SEC2 to the furnace control CPU (not atW/W1, G, R, etc.).If flame is proved wh

Seite 34

This furnace must be installed with a direct-vent (combustion airand flue) system and a factory accessory termination kit. In adirect-vent system, all

Seite 35

energize the Y/Y2 terminal and switch the outdoor unit tohigh-cooling, as long as the thermostat continues to call forcooling. Subsequent selection is

Seite 36

When the thermostat ″calls for high-cooling″, the blower motorBLWM will operate at high-cooling airflow. When the thermostatis satisfied, the blower m

Seite 37

A00275Fig. 54—Two-Stage Furnace with Single-SpeedAir ConditionerFig. 55—Two-Stage Furnace with Two-SpeedAir ConditionerA00276A00277Fig. 56—Two-Stage F

Seite 38

A00279Fig. 58—Dual Fuel Thermostat with Two-StageFurnace and Single-Speed Heat PumpA00281Fig. 60—Two-Stage Thermostat With Two-StageFurnace and Two-Sp

Seite 39

Notes for Fig. 54-61:1. Heat pump MUST have a high pressure switch for dual fuel applications.2. Refer to outdoor equipment Installation Instructions

Seite 40

AVG. GAS SPECIFIC GRAVITY OF NATURAL GASHEAT VALUE 0.58 0.60 0.62 0.64AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice

Seite 41

AVG. GAS SPECIFIC GRAVITY OF NATURAL GASHEAT VALUE 0.58 0.60 0.62 0.64AT ALTITUDE Orifice Mnfld Press Orifice Mnfld Press Orifice Mnfld Press Orifice

Seite 42

e. Turn low-heat adjusting screw (3/32 hex Allen wrench)counterclockwise (out) to decrease input rate or clock-wise (in) to increase input rate.NOTE:

Seite 43 - See note 2

NOTE: Clocking gas input rate MUST always be performed withthe burner box cover INSTALLED.c. Check that gas valve adjustment caps are in place forprop

Seite 44 - Notes for Fig. 54-61:

b. Check derate for altitude if applicable.c. Check all return and supply ducts for excessive restric-tions causing static pressure greater than 0.5-i

Seite 45

For accessory installation details, refer to accessory installationinstructions.CODES AND STANDARDSFollow all national and local codes and standards i

Seite 46

CHECKLIST—INSTALLATIONLOAD CALCULATION____________ Heating Load (Btuh)____________ Cooling Load (Btuh)____________ Furnace Model SelectionCOMBUSTION A

Seite 48

A94328SERVICE TRAININGPackaged Service Training programs are an excellent way to increase yourknowledge of the equipment discussed in this manual, inc

Seite 49

4. If you touch ungrounded objects (recharge your body withstatic electricity), firmly touch furnace again before touch-ing control or wires.5. Use th

Seite 50 - CHECKLIST—INSTALLATION

1. Collector Box Drain, Inducer Housing Drain, Relief Port,and Pressure Switch TubesThese tubes should be factory attached to condensate trapand press

Seite 51

3. Install casing hole filler cap (factory-supplied in loose partsbag) into blower shelf hole where trap was removed.WARNING: CARBON MONOXIDE POISONIN

Seite 52 - SERVICE TRAINING

(2.) Condensate Trap Located on Right Side of Casing(a.) Install drain tube coupling (factory-supplied inloose parts bag) into collector box drain tub