NOTE: Read the entire instruction manual before starting theinstallation.SAFETY CONSIDERATIONSImproper installation, adjustment, alteration, service,
4. Close electrical disconnects to energize system.5. Set room thermostat at desired temperature. Be sure the setpoint is below indoor ambient and is
Adjust charge in both heating and cooling by following procedureshown on charging tables located on pink charging label on backside of access panel.NO
NOTE: When two-speed unit is operating in low-capacity cool-ing, system vapor (suction) pressure will be higher than a standardsingle-speed system or
After termination of a defrost cycle, the outdoor fan delays comeon for 20 sec. This allows refrigerant system to recover outdoorcoil heat and minimiz
XIV. FINAL CHECKSIMPORTANT: Before leaving job, be sure to do the following:1. Ensure that all wiring and tubing is secure in unit beforeadding panels
→ Fig. 18—Wiring Diagram—024, 036, 048A03030—15—
→ Fig. 19—Wiring Diagram—060A03031OCT-t∞LPSHPSOAT-t∞LOHITO INDOOR UNITREDCCHFAN CAPREDBRNOFMBLKBLU/PNKBLU/PNKYEL/PNKBRNBRNBLKBLKRVSORNREDBLUCH11212313
INSTALLATIONI. CHECK EQUIPMENT AND JOB SITEA. UNPACK UNITMove to final location. Remove carton, taking care not to damageunit.B. INSPECT EQUIPMENTFile
VI. CHECK INDOOR EXPANSION DEVICECAUTION: For proper unit operation and reliability,units must be installed with balance port hard shutoffTXV specific
of the Long-Line Guideline section in the Application Guidelineand Service Manual for Residential Split-System Air Conditionersand Heat Pumps Using Pu
C. REFRIGERANT TUBING AND FILTER DRIERCAUTION: Installation of filter drier in liquid line isrequired.Connect vapor tubing to fittings on outdoor unit
DEEP VACUUM METHODThe deep vacuum method requires a vacuum pump capable ofpulling a vacuum of 500 microns and a vacuum gage capable ofaccurately measu
NOTE: Install branch circuit disconnect of adequate size perNEC to handle unit starting current. Locate disconnect within sightfrom and readily access
24 VAC HOTFANRGRG24 VAC COMMN/AOUTDOORSENSORCONNECTIONCBS1S2C CRPROGRAMMABLETHERMOSTATMODEL 2SFV4FK4FAN COILJ1JUMPERJ2 JUMPERTWO-SPEEDHEAT PUMPDHY1Y1W
O/W2W/W1Y1/W2GRVARIABLE-SPEEDCONDENSINGFURNACETWO-SPEEDHEAT PUMPW/W1GY/Y2CY2RY1W1OCDHUMHUMBS1S2W2RHEAT STAGE 3COOL/HEATSTAGE 1COOL/HEATSTAGE 2RVS COOL