Installation Instructions187B (2 -- 5 TONS)180B (3 TON TROPHY)EVOLUTIONt SERIES 2--STAGE AIR CONDITIONERWITH PURONRREFRIGERANTSAFETY CONSIDERATIONSImp
10cutout trips for three consecutive cycles, then unit operation islocked out for 4 hours and the appropriate fault code is displayed.No 230V at Compr
11OAT Thermistor must belocked in place with sphericalnib end facing towards thefront of the control boxFig. 8 -- Outdoor Air Thermistor (OAT) Attachm
12T h e r m i di s ta t M o de l s T 6 --- P R H0 1 --- A & T 6 --- N RH 0 1 --- Aw/ VS Fan Coil & 2---Stage Air ConditionerT h e r m i di s t
13PURONR (R--410A) REFRIGERANT QUICK REFERENCE GUIDES Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing
14Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.E2
2The outdoor unit contains system refrigerant charge for operationwith AHRI rated indoor unit when connected by 15 ft. (4.57 m) offield--supplied or f
3Table 1 – Accessory UsageACCESSORYREQUIRED FORL O W --- A M B I E N T C O O L I N GAPPLICATIONS(Below 55°F/12.8_C)REQUIRED FOR LONG LINEAPPLICATIONS*
4Refer to Fig. 3 and install filter drier as follows:1. Braze 5--in. liquid tube to the indoor coil.2. Wrap filter drier with damp cloth.3. Braze filt
5Final Wiring CheckIMPORTANT: Check factory wiring and field wire connectionsto ensure terminations are secured properly. Check wire routing toensure
6Communication and Status Function LightsFor Evolution Control Only, Green communications(COMM)LightGreen LED (COMM Light)A green LED (COMM light) on
7UTILITY RELAY *UTILITY SIGNALOPEN RELAY* SUPPLIED BY UTILITY PROVIDERMODEL PLUGLLSLiquid Line SolenoidMODEL PLUGA06526Fig. 6 -- 2--Stage Control Boa
8Final ChecksIMPORTANT: Before leaving job, be sure to do the following:1. Ensure that all wiring is routed away from tubing and sheetmetal edges to p
9TROUBLESHOOTINGIf the compressor fails to operate with a cooling call, Table 4 can beused to verify if there is any damage to the compressor windings