Section 2 START-UP AND OPERATION STEAM BOILERS
3.5 BOILER WATER TREATMENT PURPOSE OF WATER TREATMENT Water treatment is required for satisfactory operation of the boiler. It must be d
3.7 SUGGESTED MAINTENANCE SCHEDULE DAILY 1. Make visual inspection of gauges, monitors, and indicators and record readings in boiler log.
3.8 FLOAT-ACTUATED WATER LEVEL CONTROLS Inspect float type water level controls for proper operation. Visually inspect sight glasses fo
4.0 IDLE BOILER CARE AND LAY-UP GENERAL Corrosion damage to boilers is often the result of improper lay-up during non-operating periods.
lay-up. Raw city water is not recommended and should not be used. Prepare the chemical solution described in (1a) in a separate tank. Ad
An alternate method is to completely dry a clean boil (by blowing hot dry air though the boiler) and then purge the air from the boiler
NOTE THE LOW FIRE ADJUSTMENT SHOULD RESULT IN A GAS PRESSURE ON THE BURNER MANIFOLD EQUAL TO 1" WATER COLUMN FOR NATURAL GAS AND 3&q
2.3 SAFETY SHUT-OFF DEVICES (FLAME SUPERVISION) 2.3.1 FLAME SUPERVISORY SYSTEM The boiler is equipped with a flame supervisory system,
Water Cut-off controls, particularly installing, operating and servicing. 2.4.6 OTHER CONTROLS Additional controls as required for the p
FORCED DRAFT OIL FIRED BOILERS BOILER SERIES DRAFT AT BOILER OUTLET (i.w.c.) CO2 @ HIGH FIRE O2 @ HIGH FIRE CO (ppm) SMOKE NO. D -0.01
2.6 OPERATING INSTRUCTIONS 2.6.1 FAMILIARIZATION WITH MANUAL(S) The user of the boiler must familiarize himself with this manual and t
CARE AND MAINTENANCE STEAM BOILERS
CAUTION The boil out procedure outlined must be performed by, or under the direct supervision of, a qualified technician. The chemicals
3.3 SYSTEM CLEAN OUT Many boilers have been ruined with system contaminants such as pipe dope, cutting oil, metal shavings or chips and