Bryant 542E Bedienungsanleitung Seite 5

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 16
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 4
ACOUSTIC a INSULATION
DUCT LINER
tween the ductwork and unit to prevent transmission of
vibration. The duct system can be screwed or bolted to
the unit duct flanges. Suitable gaskets should be used to
insure an airtight seal. When a supplemental electric
resistance heater is being used, use fireproof material
for the connector between the ductwork and unit sup
ply-air duct flange. If flexible duct (which is not heat re
sistant) is being used, use a sheet metal duct sleeve in
side the flexible duct for at least the first 36 inches of
duct.
3. An external field-supplied air filter must be installed in
the 542E return-air ductwork. Recommended filter sizes
are shown in Table I. Filters should be installed where
they are easily accessible for service.
NOTE: Model 542D has factory-supplied high-capacity air
filters. High-capacity air filters are also factory-supplied
when the accessory plenum, horizontal economizer, or high-
capacity filter rack is being used with Model 542E.
4. Avoid abrupt duct size increases of decreases.
5. Size all ductwork for required heat pump airflow.
6. Adequately insulate and weatherproof all ductwork
located outdoors. Ducts passing thru an unconditioned
space must be insulated and covered with a vapor bar
rier in accordance with the latest issue of SMACNA and
NESCA minimum installation standards for heating
and air conditioning systems.
7. Secure all ducts to the building structure.
8. All openings in the building structure must be properly
flashed, weatherproofed, and vibration-isolated in ac
cordance with local codes and good building practices.
IV. ELECTRICAL CONNECTIONS
WARNING: Tlit- iiiiit l aliinet have.-in uninrerrupted or
unbroken electrical ground to mininii/o por.ional injury if aii
electrical fault should occur. This may consist of elec.rical
wire connected to the unit ground lug in the control com
partment, or conduit approved for electrical ground when in
stalled in accordance with the National Electrical Code and
local electrical codes. A failure to follow this warning can re
sult, in the installer being liable for the personal injury .of
others. ■ , ■ ,
CAUTiON: A failure to follow these precautions could result
in danaage to the. unit being installed:
1. All electrical connections must be made in accordance
with the National Electrical Code and local electrical
codes governing such wiring.
2. Copper conductor is the only type of wire that is to be
connected between the field-supplied electrical discon
nect switch and the unit. DO NOT USE ALUMINUM
WIRE.
3. High-voltage power to the unit must be within the
operating voltage range indicated on the unit rating
plate. On 3-phase units, phases must be balanced within
2%. Consult the local power company for correction of
improper voltage and/or phase balance.
4. When the low-voltage control wires are run in the same
conduit as the high-voltage wires, the low-voltage wires
must be insulated for the highest voltage contained
within the conduit.
Figure 10—542E Typical Rooftop
Installation on Pitched Roof
5. When drilling thru any panel to mount electrical hard
ware, conduit, etc; ensure that the drill does not damage
internal components.
6. If aluminum ,conductors are used between the electrical
service panel (power source) and the field-supplied
electrical disconnect switch, the wire gauge selected
must have a current capacity that is not less than the
; copper wire specified and must not create a; voltage drop
in excess of 2% of the unit rated voltage.
A. High-Voltage Connections
A separate electrical line with a field-supplied, waterproof,
fused disconnect, switch mounted at, or within sight of, the
unit must be used for this installation. Refer to the unit rat
ing plate for maximum fuse size and minimum amps
(ampacity) for wire sizing. Tables II and III show recom
mended wire sizes and lengths based on rating plate data.
NOTE: The field-supplied fused disconnect may be mounted
over the unit high-voltage inlet hole directly on the control
corner panel adjacent to the blower access panel. See Figure
3 or 4. Be sure that the disconnect box does not interfere
with the removal of the blower access panel. When mount
ing the disconnect box, align the knockout in the box with
the unit high-voltage inlet hole. Route the wiring from the
disconnect box thru the aligned holes. This connection must
be watertight to prevent water from entering the control
box.
Proceed as follows to complete the high-voltage connections
to the unit:
1. Run high-voltage power leads from fused disconnect
thru high-voltage inlet hole in control corner panel. See
Figure 3 or 4.
2. Connect ground lead to chassis ground connection, and
connect high-voltage power leads to unit high-voltage
pitgail leads. Single-phase units have two black pigtail
leads. Three-phase units have two black and one red pig
tail lead. See Figure 12, Figure 13, and unit wiring
label. Use a suitable wire splice connector or wirenut to
make each high-voltage connection. Tape each com
pleted connection.
B. Low-Voltage Connections
Recommended heat pump room thermostats for heat pump
operation with or without supplemental electric heaters are
P/N 34427DP115 (subbase included) for automatic system
changeover and P/N34427DP118 (subbase included) for
manual system changeover. These thermostats have an
emergency heat (EM. HT.) switch and red indicator light.
Heat pump room thermostat P/N 34427DP87 (subbase in
cluded) can be used for heat pump operation without supple
mental electric heaters. This thermostat provides for
manual system changeover and does not have an emergency
heat switch.
-5-
Seitenansicht 4
1 2 3 4 5 6 7 8 9 10 ... 15 16

Kommentare zu diesen Handbüchern

Keine Kommentare