A. 551A, 559F, 579F, and 581A Units
1. Install accessory 0° F low-ambient kit (part no. 389221-
701) per instructions supplied with kit.
2. Identify black wire from outdoor fan motor (OFM1).
Motor location is shown in Fig. 1. The OFM1 is the fan
located on the filter access side of the unit.
3. Trace black wire to wiring harness near head pressure
controller location.
4. Splice head pressure controller into black wire from OFM1
in 2 places as shown in Fig. 5 with wirenuts supplied.
5. Replace all panels on unit and turn power on.
B. 542J Units (See Fig. 6)
1. Install accessory 0° F Low Ambient Kit (part
no. CRLOWAMB001A00) per instructions supplied with
kit.
2. Locate the black wire from the outdoor-fan motor (OFM1)
to terminal OFC-11. The OFM1 is the fan located on the
filter access side of the unit. Remove the wire from ter-
minal OFC-11 and reconnect it to terminal HC-11 as
shown in Fig. 6.
NOTE: The black leads for OFM2 and OFM3 are labeled with
a factory-supplied wire marker.
3. Using field-supplied wire, make a connection between
terminals OFC-11 and HC-21.
4. Using 2 field-supplied wires and the factory-supplied wire-
nuts, splice one of the 2 head pressure control device
leads to terminal HC-21, and the other to terminal HC-11
as shown in Fig. 6.
5. Replace all panels on unit and turn power on.
Fig. 4 — Sensor Location on Outdoor Coil
Hairpin Bend, 559F and 579F Units
LEGEND
CAP — Capacitor
OFM — Outdoor-Fan Motor
QT — Quadruple Terminal
Accessory Low-Ambient Wiring
Splice
Fig.5—Wiring Diagram; 551A, 559F, 579F, and 581A Units
—3—