connected to one of the dry contact terminals. The other dry contact terminal is
connected to the dehumidify terminal on the furnace or fan coil. This provides
power to energize the dehumidify terminal on the cooling equipment when the
dry contact is closed.
If it is desired to operate a ventilator or other device, the D1 and D2 terminals
can be connected directly to the equipment. This will provide a closed contact
for the specified number of minutes per hour. See Option 19.
If timed control of the system blower is required, the dry contact can be used for
this function. The G terminal can be connected to one of the dry contact
terminals with the other terminal being connected to Rc and/or Rh for timed
control of the fan. Note that this is not the same as programmable fan Option 30.
See Wiring Diagrams for more information.