seconds. The control will operate from the temperature sensed by the working
sensor.
E1 -- If the Display Module and the Equipment Control Module cannot
communicate via two--wire connection, an E1 will be displayed.
E2 --ThereisnoE2errormessage.
E3 -- If Thermidistat Control cannot properly read outdoor temperature, and it is
needed for proper operation, display will indicate “---- ” in the outdoor
temperature location.
E4 -- If Thermidistat Control’s internal memory fails, E4 will be displayed.
Replace Thermidistat Control.
E5 -- If Thermidistat Control cannot properly read humidity, E5 will be
displayed. Replace Thermidistat Control. If both Humidify and Dehumidify
have been set to OF, the humidity value will be shown as “---- ” when viewed
from the humidity menu, but no E5 will be shown in the display.
Table 4 can be used as a troubleshooting tool for determining which outputs will
be active for a particular configuration and each operating mode.