7. The adjacent chart specifies
the maximum pressure (high
fire) and minimum pressure
(low fire) for the burner opera-
tion. The Combination Control
modulates the pressure to the
burner between this mini-
mum/maximum range based on
ambient temperature, refrigera-
tor load, and thermostat setting.
8. Access to the combination con-
trol is gained by removing (2)
knobs and (6) screws as shown
in Figure 3.18. The Combination
Control needs not be removed
for the pressure check.
9. Use a 3/16" allen wrench to
remove the plug and a 1/8"
NPT nipple to install in pres-
sure tap fitting.
10. Figure 3.29A represents a possible defective combination control, a
clogged gas filter or a kinked supply line. Figure 3.29B indicates proper
gas pressure in a properly functioning refrigerator.
B101
Gas Pressure Settings For Refrigerator
(Inlet Gas Pressure at 11"W.C.)
Model High Fire Low Fire
442, 443 10.5" To 10.9" W.C. 1.2" To 2.4" W.C.
452, 453 10.5" To 10.9" W.C. 1.2" To 2.4" W.C.
462, 463 10.5" To 10.9" W.C. .8" To 1.8" W.C.
482, 483 10.5" To 10.9" W.C. .8" To 1.8" W.C.
See Step # 7 for proper operation of combination control
Figure 3.29A Incorrect Manometer Reading
(warm refrigerator)
Figure 3.29B Correct Manometer Reading
3-14