Bryant TSTATBBN2S01-C Installationshandbuch Seite 22

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 68
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 21
Residential H&V - 60Hz R22 & R410A - Geothermal Heat Pumps - Rev.: 21 Aug, 2007D
22
GROUND-LOOP HEAT PUMP APPLICATIONS
Table 2: Antifreeze Percentages by Volume
Low Water Temperature Cutout Setting
CXM or DXM Control
When antifreeze is selected, the FP1 jumper (JW3)
should be clipped to select the low temperature
(antifreeze 13°F [-10.6°C]) set point and avoid nuisance
faults (see “Low Water Temperature Cutout Selection” in
this manual). NOTE: Low water temperature operation
requires extended range equipment.
pressure is reached. Open the return valve and a
pressure surge will be sent through the loop to help
purge air pockets from the piping system.
4. Notice the drop in uid level in the ush cart tank
when the return valve is shut off. If air is adequately
purged from the system, the level will drop only 1-2
inches (2.5 - 5 cm) in a 10” (25 cm) diameter PVC
ush tank (about a half gallon [2.3 liters]), since
liquids are incompressible. If the level drops more
than this, ushing should continue since air is still
being compressed in the loop uid. Perform the “dead
head” procedure a number of times.
Note: This uid level drop is your only indication of air in
the loop.
Antifreeze may be added before, during or after the
ushing procedure. However, depending upon which time
is chosen, antifreeze could be wasted when emptying the
ush cart tank. See antifreeze section for more details.
Loop static pressure will uctuate with the seasons.
Pressures will be higher in the winter months than
during the cooling season. This uctuation is normal and
should be considered when charging the system initially.
Run the unit in either heating or cooling for a number
of minutes to condition the loop to a homogenous
temperature. This is a good time for tool cleanup, piping
insulation, etc. Then, perform nal ush and pressurize
the loop to a static pressure of 50-75 psi [345-517 kPa]
(winter) or 35-40 psi [241-276 kPa] (summer). After
pressurization, be sure to loosen the plug at the end of
the Grundfos loop pump motor(s) to allow trapped air to
be discharged and to insure the motor housing has been
ooded. This is not required for Taco circulators. Insure
that the Flow Controller provides adequate ow through
the unit by checking pressure drop across the heat
exchanger and compare to the pressure drop tables at
the back of the manual.
Antifreeze
In areas where minimum entering loop temperatures drop
below 40°F [5°C] or where piping will be routed through
areas subject to freezing, antifreeze is required. Alcohols
and glycols are commonly used as antifreeze; however
your local sales manager should be consulted for the
antifreeze best suited to your area. Freeze protection
should be maintained to 15°F [9°C] below the lowest
expected entering loop temperature. For example, if
30°F [-1°C] is the minimum expected entering loop
temperature, the leaving loop temperature would be 25 to
22°F [-4 to -6°C] and freeze protection should be at 15°F
[-10°C]. Calculation is as follows:
30°F - 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from
a reservoir outside of the building when possible or
introduced under the water level to prevent fumes.
Calculate the total volume of uid in the piping system.
Then use the percentage by volume shown in Table
1 for the amount of antifreeze needed. Antifreeze
concentration should be checked from a well mixed
sample using a hydrometer to measure speci c gravity.
Table 1: Approximate Fluid Volume (gal.)
per 100' of Pipe
Type
Minimum Temperature for Low Temperature Protection
10°F [-12.2°C] 15°F [-9.4°C] 20°F [-6.7°C] 25°F [-3.9°C]
Methanol
100% USP food grade Propylene Glycol
Ethanol*
25%
38%
29%
21%
25%
25%
16%
22%
20%
10%
15%
14%
* Must not be denatured with any petroleum based product
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)
Pipe Size Volume (gal) [liters]
Copper
1” 4.1 [15.3]
1.25” 6.4 [23.8]
2.5” 9.2 [34.3]
Rubber Hose 1” 3.9 [14.6]
Polyethylene
3/4” IPS SDR11 2.8 [10.4]
1” iPS SDR11 4.5 [16.7]
1.25” IPS SDR11 8.0 [29.8]
1.5” IPS SDR11 10.9 [40.7]
2” IPS SDR11 18.0 [67.0]
1.25” IPS SCH40 8.3 [30.9]
1.5” IPS SCH40 10.9 [40.7]
2” IPS SCH40 17.0 [63.4]
Unit Heat Exchanger Typical 1.0 [3.8]
Flush Cart Tank
10” Dia x 3ft tall
[254mm x 91.4cm tall]
10 [37.9]
Seitenansicht 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 67 68

Kommentare zu diesen Handbüchern

Keine Kommentare