10.(All wires are color coded and
labeled with amperage and voltage to
make connection easy.) Simply
disconnect the black wire from the
circuit breaker in the main panel and
reconnect it to the appropriate wire
from the emergency load center with
a wire nut. Repeat this step for the
rest of the circuits to be run by the
generator.
11.Install the 40 Amp or 70 Amp
double pole circuit breaker into the
main electrical distribution panel. This
circuit breaker must be compatible
with your main electrical distribution
panel. Switch off the circuit breaker.
Connect white wire to the main
distribution panel neutral bar.
Connect the green wire to the main
electrical panel ground bar. Connect
the black and red wires to the 40
Amp or 70 Amp double pole circuit
breaker. All indoor wiring is now
complete.
DON’T FORGET...
Remove fuses in control panel
• Connect starting battery
Open fuel valve
Reinstall fuses in control panel
Set generator mode switch to “AUTO”
Set exercise timer - Switch on service
main circuit breaker, the circuit
breakers in your main panel and
circuit breakers in the load center.
21
INSTALLATION CONT.
EXERCISER
SWITCH
FUEL VALVE