Power Exhaust Test
This point allows the board’s power exhaust (PE) output
to be manually turned On (Enable) and Off (Disable).
Power Exhaust test can operate simultaneously with other
Service Test Points.
Economizer Test
This point allows the board’s economizer output to be
manually controlled from 0 to 100 % Open. Economizer test
can operate simultaneously with other Service Test Points.
VFD Speed Test
This point activates the board’s 0--10vdc analog output
that controls the unit’s supply fan VFD speed.
NOTE: This output is only applicable if Fan Control is
set to Variable Speed.
NOTE: Service Test Mode does not timeout. Be sure to
turn off test mode or cycle power to the RTU to return to
normal operation.
Configuration
The RTU Open controllers configuration points effect the
unit’s inputs and operation. Review and understand the
meaning and purpose of each configuration point before
changing it from the factory default value. Use the RTU
Open Start-up Sheet during configuration; fill in changed
values if changed from factory default. There are three main
configurations menus: SETPOINT, UNIT, and SERVICE.
Each configuration point is described below under its
according menu. See Appendix A for menu structure.
Setpoint
Occupied Heating Setpoint -- The heating setpoint the
controller maintains during the occupied period.
Range = 40 - 90_F Default = 70_F
Occupied Cooling Setpoint The cooling setpoint the
controller maintains during the occupied period.
Range = 55 - 99_F Default = 76_F
Unoccupied Heating Setpoint The heating setpoint the
controller maintains during the unoccupied period.
Range = 40 - 90_F Default = 55_F
Unoccupied Cooling Setpoint The cooling setpoint the
controller maintains during the unoccupied period.
Range = 45 - 99_F Default = 90_F
Effective Heating Setpoint The current setpoint value
heating operation will control to.
Range = 0 - 120_F
Effective Cooling Setpoint The current setpoint value
cooling operation will control to.
Range = 0 - 120_F
Optimal Start - The earliest time prior to occupancy, at
which the Optimal Start function may begin to adjust the
effective setpoints. Setting this to 0 will disable optimal start.
Range = 0 - 4 hours Default = 4 hour
Occ Relative Humidity Setpoint The space RH setpoint
the controller maintains during the occupied period.
Range = 0 to the Unocc RH setpoint
Default 60%
Unocc Relative Humidity Setpoint The space RH
setpoint the controller will maintain during the
unoccupied period.
Range = 30-100% Default = 95%
DCV Max Ctrl Setpoint – The difference between indoor
and outdoor CO
2
level which results in maximum
ventilation damper position.
Range = 0-9999ppm Default = 650ppm
Power Exhaust Setpoint –Usedtodeterminewhenthe
power exhaust operation will begin. This setpoint is based
on the maximum fan speed. When the economizer
position opens above this point, power exhaust operation
will begin and when the damper position falls 5% below
this point, the power exhaust will shutdown.
Range = 20-90% Default = 50%
NOTE: This setpoint is automatically adjusted if the Fan
Type is set to Variable Speed or 2--Speed in order to
maintain proper building pressure. The actual calculated
value, Calculated PE Setpoint, is shown in
MAINTENANCE.
NOTE: This point is only used when Continuous
Occupied Exhaust = NO
Unit
Fan Mode – Sets the operation of the indoor fan when not
in cooling or heating mode. Refer to fan operation for
details on each operation.
Range = Auto, Continuous, or Always On
Default = Continuous
Power Fail Restart Delay -- Sets how long the controller
delays normal operation after the power is restored.
Typically used to prevent excessive demand when
recovering from a power failure
Range = 0 - 30 sec Default = 5 sec
Fan Off Delay Time delay in which the fan will
continue run after being commanded off.
Range = 10 -300 sec Default = 90 sec
Minimum Cooling SAT The supply air temperature
must remain above this value to allow cooling with the
economizer and/or compressors. There is 5_Fplusand
minus deadband to this point. If the SAT falls below this
value during cooling a compressor stage will be removed
and/or the economizer will return to minimum position.
Range = 45 - 75_F Default = 50_F
Maximum Heating SAT The supply air temperature must
remain below this value to allow heating. There is 5_Fplus
and minus deadband to this point. If the SAT falls below this
value during heating the heat stages will begin to decrease
until the SAT has dropped below this value.
Range = 85 - 150_F Default = 120_F
Vent Dmpr Pos / DCV Min Pos Minimum damper
position for ventilation during the occupied period when
the fan is operating at full speed.
Range = 0 -- 100% open Default = 20% open
Economizer Purge Min Pos The damper position used
during the Pre--Occupancy Purge cycle prior to occupancy
when Pre--Occupancy purge is active
Range = 0 -- 100% open Default = 40% open
Low Fan Econ Min Pos – The minimum damper position
used for ventilation during the occupied period when the
fan is operating at it’s lowest speed.
Range = 0 -- 100% open Default = 33% open
NOTE: This setpoint is only applicable if the Fan Type is
set to Variable Speed or 2--Speed.
TS---5580J---02