Table 4 -- RTU Open Alarms (cont)
POINT NAME
BACnet Object
NAME
ACTION TAKEN BY
CONTROL
RESET METHOD PROBABLE CAUSE
Indoor Air Quality Sen sor iaq_sensor_fail No IAQ Operation Automatic Sens o r reading is out of range. Bad
sensor, bad wiring, failure to recei v e
Network or sensor configured incorrectly.
Outdoor Air Quality Sensor oaq_fail Control uses default OAQ valu e of
400 ppm.
Automatic Sensor reading is out of range. Bad
sensor, bad wiring, failure to receive
Networkvalue,orsensorconfigured
incorrectly.
Economizer Operation econ_opr Alert Gener ated Automatic This al arm is active whenever an
economizer fault is detected as required
by the California Title 24 Economizer
FDD logic.
Economizer f ault conditions include;
Failed to Fully Open, Failed to Open,
Failed to Close, and Stuck Open.
Space Temperature spt_alrm_status Alert Generated Automati c Space Temperatu re value is less than
the low limit value or greater than the
high limit value
Supply Air Temperature sat_alarm Alert Generated Automatic SAT is greater than the high limit value
or less than the low limit value for more
than 5 minutes
Setpoint Slider slidepot_alarm Set Offset to zero Automatic STO sensor is open for more than 5
seconds
Switch Configuration di_cfg_alarm Disable only wrong switch
functions
Configure correctly More than one discrete input is confi g ure d
to provide the same function.
Analog Input
Configuration
ai_cfg_alarm Disable 4 selectable analog inputs Configure correctly More than one analog input is
configured to provide the same
function.
Space Relative Humidity sprh_hi_alarm Alert Generated Automatic Indoor RH is greater than the high limit
value or less than the low limit value for
more then 15 minutes
Indoor Air Quality iaq_alarm Alert Gener ated Automatic CO
2
ppm reading is above the
configuration for 1 minute
Supply Fan Runtime sfan_rntm_alarm Alert Gener ated zero the timer Supply fan run time exceeded user
defined limit
Compressor 1 Runtime comp1_rntm_alarm Alert Gener ated zero the timer Compressor #1 run time li mit is exceeded
Compressor 2 Runtime comp2_rntm_alarm Alert Gener ated zero the timer Compressor #2 run time li mit is exceeded
Filter filter_alarm Alert Gener ated Automatic / res et
timer
Dirty Filter, supply fan run time exceeded,
filter switch configuration wrong.