APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)
RTU Open Protocol Maps
Point Name
Point
Access
Units
BACnet Info Modbus Info N2 Info LonWorks Info
BACnet
Point Name
BACnet
Object ID
Modbus Register Type
Modbus
Register #
N2 Network
Point Type
N2 Network
Point
Address
SNVT Type SNVT Name
SPT Sensor Read Only min zone_temp_over-
ride_time_remaining
AV:1 Select.. Select.. Select
Stage 1 SAT Stpt R/W °F stg_1_sat AV:83008 Input Register (Float) 161 ADF 66 Select
Stage 2 SAT Stpt R/W °F stg_2_sat AV:83009 Input Register (Float) 157 ADF 64 Select
Stage 3 SAT Stpt R/W °F stg_3_sat AV:83010 Input Register (Float) 159 ADF 65 Select
Supply Air Temperature Read Only °F sa_temp AV:1008 Input Register (Float) 109 ADF 49 SNVT_temp_p(105) nvoSAT
Supply Fan Runtime Read Only hr sfan_rntm AV:2014 Input Register (Float) 111 ADF 50 Select
Supply Fan Service Alarm Timer R/W hr sfan_service_hrs AV:83005 Holding Register (Float) 113 ADF 51 Select
Supply Fan VFD Read Only % vfd_output AV:2027 Input Register (Float) 91 ADF 33 Select
System Cooling Demand Level Read Only no units cool_demand_level AV:9006 Input Register (Float) 115 ADF 52 Select
System Heating Demand Level Read Only no units heat_demand_level AV:9036 Input Register (Float) 117 ADF 53 Select
System OAT Master Read Only °F mstr_oa_temp AV:80001 Input Register (Float) 121 ADF 55 Select
System Outdoor Air Temperature R/W °F system_oat AV:1901 Holding Register (Float) 119 ADF 54 SNVT_temp_p(105) nviSysOAT
System Outdoor AQ R/W no units system_oaq AV:1908 Holding Register (Float) 155 ADF 63 Select
System Space AQ R/W no units system_iaq AV:1903 Holding Register (Float) 149 ADF 39 SNVT_count_inc(9) nviSysSpAQ
System Space RH R/W % system_rh AV:1904 Holding Register (Float) 151 ADF 40 SNVT_lev_percent(81) nviSysSpRH
System Space Temperature R/W °F system_spt AV:1902 Holding Register (Float) 123 ADF 56 SNVT_temp_p(105) nviSysSpTmp
T5x Override Duration R/W hr ovr_dur AV:9023 Holding Register (Float) 125 ADF 57 Select
Unocc Relative Humidity Setpoint R/W %rh unocc_dehum_stpt AV:3012 Holding Register (Float) 129 ADF 59 SNVT_lev_percent(81) nviUnoccRHSP
Vent Dmpr Pos / DCV Min Pos R/W %Open econ_min AV:9005 Holding Register (Float) 131 ADF 60 SNVT_lev_percent(81) nviDCVMinPos
VFD Speed Test R/W % vfd_spd_test AV:81002 Holding Register (Float) 153 ADF 62 Select
input_3 Read Only di_3 BI:1003 Discrete Input 1 BI 1 Select
input_4 Read Only di_4 BI:1004 Discrete Input 2 BI 2 Select
input_5 Read Only di_5 BI:1005 Discrete Input 3 BI 3 Select
input_8 Read Only di_8 BI:1008 Discrete Input 4 BI 4 Select
input_9 Read Only di_9 BI:1009 Discrete Input 5 BI 5 Select
Airside Linkage Read Only air_linkage_fail BV:7030 Discrete Input 26 BI 26 Select
Analog Input Configuration Read Only ai_cfg_alarm BV:7026 Discrete Input 36 BI 36 Select
Compressor 1 Relay State Read Only comp_1 BV:2005 Discrete Input 6 BI 6 Select
Compressor 1 Runtime Read Only comp1_rntm_alarm BV:7014 Discrete Input 28 BI 28 Select
Compressor 1 Test R/W comp1_test BV:81005 Coil 1 BO 1 Select
Compressor 2 Relay State Read Only comp_2 BV:2004 Discrete Input 7 BI 7 Select
Compressor 2 Runtime Read Only comp2_rntm_alarm BV:7015 Discrete Input 29 BI 29 Select
Compressor 2 Test R/W comp2_test BV:81004 Coil 2 BO 2 Select
Compressor Safety Status Read Only comp_status BV:1008 Discrete Input 8 BI 8 Select
Compressor Status Read Only comp_alarm BV:7013 Discrete Input 30 BI 30 SNVT_switch(95) nvoCmpSafety
Continuous Occupied Exhaust R/W occ_exh BV:9002 Coil 3 BO 3 Select
DCV Control R/W dcv_enable BV:1027 Select.. Select.. Select
Dehumidification Read Only dehum BV:2006 Discrete Input 9 BI 9 Select
Dehumidification Test R/W dehum_test BV:81006 Coil 4 BO 4 Select
Door Contact Status Read Only door_contact_status BV:1010 Discrete Input 10 BI 10 Select
Economizer Exists R/W econ_exist BV:99001 Coil 5 BO 5 Select
Economizer Operation Read Only econ_opr BV:7054 Select.. Select.. Select
Enthalpy (BACnet) R/W oae BV:1901 Coil 6 BO 6 SNVT_switch(95) nviSysEnth
Enthalpy Status Read Only enthalpy_status BV:1002 Discrete Input 11 BI 11 Select
Factory Test R/W fac_test_enable BV:91000 Coil 7 BO 7 Select
Factory Test Relay 1 Control R/W relay1_fac_test BV:91001 Coil 8 BO 8 Select
Factory Test Relay 2 Control R/W relay2_fac_test BV:91002 Coil 9 BO 9 Select
Factory Test Relay 3 Control R/W relay3_fac_test BV:91003 Coil 10 BO 10 Select
Factory Test Relay 4 Control R/W relay4_fac_test BV:91004 Coil 11 BO 11 Select
Factory Test Relay 5 Control R/W relay5_fac_test BV:91005 Coil 12 BO 12 Select
Factory Test Relay 6 Control R/W relay6_fac_test BV:91006 Coil 13 BO 13 Select
Factory Test Relay 7 Control R/W relay7_fac_test BV:91007 Coil 14 BO 14 Select
Factory Test Relay 8 Control R/W relay8_fac_test BV:91008 Coil 15 BO 15 Select
Filter Read Only filter_alarm BV:7017 Discrete Input 31 BI 31 SNVT_switch(95) nvoFilter
Filter Status Read Only filter_status BV:1004 Discrete Input 12 BI 12 Select
Fire / Smoke Shutdown Read Only fire_alarm BV:7007 Discrete Input 32 BI 32 SNVT_switch(95) nvoFrShtdwn
Fire Shutdown Status Read Only firedown_status BV:1005 Discrete Input 13 BI 13 Select
Gas Valve Read Only igc_alarm BV:7050 Discrete Input 40 BI 40 SNVT_switch(95) nvoGasVlvAlm
TS---5580J---02