25
Software Version
During Start-up and throughout the life of the equipment,
it may be necessary to obtain the RTU Open’s software
version. To do this a module status (Modstat) must be run
on the controller. This can be done from Field Assistant.
An example of the beginning lines of a Modstat is shown
in Fig. 18. The application software version shows the
current running software of the board. In this case the
rtum2_iv6--3_06_20140403 refers to RTU Open software
version 3_06_20140403. The last 8 digits of the number
refer to a date (YYYYMMDD). The first 4 digits are the
year (2014) and the month and day (0403), so this version
is April 3, 2014.
Communication LED’s
The LED’s indicate if the controller is speaking to the
devices on the network. The LED’s should reflect
communication traffic based on the baud rate set. The
higher the baud rate the more solid the LED’s will appear.
See Table 3.
04/11/2014 12:52:11 CM: 1
Device Instance: 1610551
Application Software Version: PRG:rtum2_iv6-3_06_20140403
Flash Archive Status: Valid on 04/11/14 12:51:12
1 PRGs loaded. 1 PRGs running.
Module status:
Firmware sections validated in flash memory
--------------------------------------------
--------------------------------------------
Boot16-H_IAR - v2.10:001 Apr 18 2013
RTU-OPEH DRIVER - v6.00:082 Aug 29 2013
C14144
Fig. 18 -- Example Modstat
TS---5580J---02