Input 5 -- This input is a discrete input and can be
configured to be one of six different functions: No Function,
Fire Shutdown, Fan Status, Filter Status, Remote Occupancy,
or Door Contact. This input can also be configured to be
either a Normally Open (N/O) or a Normally Closed (N/C)
switch. Input 5 is factory wired to pin J1-10. Field
accessories can be wired to its parallel pin J5-3.
Software Default = Fire Shutdown and N/C
Factory Default = Fire Shutdown and N/O
Input 8 -- This input is a discrete input and can be
configured to be one of six different functions: No
Function, Enthalpy Switch, Fan Status, Filter Status,
Remote Occupancy, or Door Contact. This input can also
be configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 8 is factory wired to
pin J2-6. Field accessories can be wired to its parallel pin
J5-1.
Software Default= Enthalpy Switch and N/O
Factory Default = No Function and N/O without
factory installed enthalpy sensor
Input 9 -- This input is a discrete input and can be
configured to be one of seven different functions: No
Function, Humidistat, Fan Status, Filter Status, Remote
Occupancy, or Door Contact. This input can also be
configured to be either a Normally Open (N/O) or a
Normally Closed (N/C) switch. Input 9 is factory and field
wiredtopinJ5-7.
Factory Default = Humidistat and N/O
Space Sensor Type This tells the controller what type
of space sensor is installed to run the unit. The four types
that can be used are: a standard 10k Type II thermistor
(T55), sensor with a setpoint offset slider bar (T56), or a
communicating sensor (SPT Sensor) and, ZS Sensor.
Range =T55, T56 (Use for T59), SPT Sensor,
or ZS Sensor
Default = T55
ZS Sensor Type -- The type of local space temperature
sensor.
Range =ZS Base, ZS Plus, ZS Pro
Default = None
T5x Override Duration Sets the override time duration
the unit will change from unoccupied to occupied when
the override button is pushed on the space sensor.
Range = 0-24 hours Default = 1 hour
Rnet Port -- input for communicating sensor
Range = SPT Sensor or ZS Sensor
Default= None
Service Configuration
Unit Type This tells the control what type of unit it is
controlling. Heat/Cool refers to gas and electric heat units.
HP O/B Ctrl refers to a heat pump unit which requires
reversing valve control. HP Y1/W1 Ctrl refers to a heat
pump unit whose reversing valve is built in to the cooling
or heating call. This decision is factory configured for the
specific unit type as supplied.
Compressor Stages This refers to the number of
mechanical cooling stages available on a specific unit.
Factory Default = One Stage for 1 compressor
units or Two Stages” for 2
compressor units.
Economizer Exists This indicates if there is an
economizer installed on the unit.
Factory Default =NO if no economizer, or YES if
there is an economizer installed
Fan Control -- This refers to the type of fan control for
the unit.
Range = Single Speed, Two Speed,
or Variable Speed
Factory Default = Single Speed --
(04--07 and A08--A12)
Two Speed--
(units with VFD option)
VFD Input -- Defines the electrical control signal used by
the VFD’s input.
Range = 2--10VDC or 0--10VDC
Factory Default = 2--10 VDC
Max VFD Output --ThemaximumVFDsignalRTUOpen
supplies to the VFD as a percentage of its range. The
balancer can set this to adjust the unit’s maximum airflow.
Applies to Variable Speed fan control.
Range = 33--100% Default = 100%
Min VFD Output -- The minimum VFD signal RTU Open
supplies to the VFD as a percentage of its range. The
balancer can set this to adjust the unit’s minimum airflow.
Applies to Variable Speed fan control only.
Range = 33--100% Default = 40%
Dehum Min VFD Output -- The minimum output signal
supplied by RTU Open during dehumidification as a
percentage of its range. Applies to Variable Speed fan
control only .
Range = 50--100% Default = 100%
Stage 1 SAT Setpoint -- The VFD Supply Air Setpoint
during stage 1 cooling. Must be at least 4_F greater than
Minimum Cooling SAT parameter
Range = 45 -- 75_F Default = 57_F
Stage 2 SAT Setpoint -- The VFD Supply Air Setpoint
during stage 2 cooling. Must be at least 4_F greater than
Minimum Cooling SAT parameter
Range = 45 -- 75_F Default = 57_F
Stage 3 SAT Setpoint -- The VFD Supply Air Setpoint
during stage 3 cooling. Must be at least 4_F greater than
Minimum Cooling SAT parameter
Range = 45 -- 75_F Default = 56_F
Heat Type Indicates the type of heat which is installed in
the unit. Electric is any unit without gas and a Gas unit is
one which requires gas input for heating.
Factory Default = Gas for gas units and Electric for
all other units (cooling only units and heat pumps)
TS---5580J---02